Software Manual 119
Services Tab
Manual: Requires a user to login and clear the event. An event that is not cleared will continue to generate actions if it is
level triggered. If the action is edge triggered, and this event is not cleared, then no new event action will result.
Deactivation Delay (in sec) (Required): Enter the time, in seconds, for the deactivation delay. This is also used to pre-
vent an event from oscillating between the on and off states when the process is near the alarm condition. Once an
event is active and the input condition then falls to an inactive condition, it must remain in the inactive state for this
delay period (in seconds) before the alarm will actually be considered inactive. If configured, this delay and hysteresis
must both be satisfied for the alarm to be cleared. Default valu: 0 to disable.
To move on to the next screen, click on the NEXT button.
Action Type: Select the desired Action Type for the event.
None: No action, log the event only.
Send SMS Message: Send an SMS message to a single recipient. Use multiple Events to notify more than one contact.
Write IODB Value: Write to a known IODB register.
Run Command Script: Run a Command Script that performs an Action.
SVM Alert Message: Send an alert message to the SVM server that will appear in unit history.
Choose Recipient (Required): This references another data list for a list of contacts.
Message Format: Define what type of content the Event alert message will contain.
Standard: Send only the standard informational message.
Custom: Send only the custom message as specified.
Standard + Custom: Append up to a 60 character Custom message to the standard message.
Custom Active Message (Required): Enter a custom message to be sent to the recipient(s) when the event goes
active. If appended to a standard message, the length is limited to 60 characters.
Custom Inactive Message (Required): Enter a custom message to be sent to the recipient(s) when event goes inactive.
If appended to a standard message, the length is limited to 60 characters.
Edge Triggering: Select the desired setting for this field.
Neither: Executes the action based on any edge triggering options.